Bencent Electronics Power Port fire risk and solutions
Time:2017-06-26 09:39:18 Source: Nums:2998
INTRODUCTION
In recent years, with the booming of lightning protection components and defense scheme, power port will rarely be damaged by the lightning stroke. However, the other problem is the fire accident that the voltage dependent resistor is subjected to abnormal power frequency overvoltage.
The circuit applications risk of three in one power port
The below picture is the classical three in one circuit of power port, three voltage dependent resistor plus one gas discharge tube.:
According to the equipment application environment, if the power port needs to tolerate a 5KA lightning stroke, then at least a 15A fuse is needed in circuit. The working current of a 15A fuse is 30A. That is to say the fuse cannot take a protective effect before 30A, but below 30A, the voltage dependent resistor will be fired.
Video 1: added 1000V to the loop, the fuse of
20A and 15A could not work and the voltage-sensitive fired.
The applications risk of T-MOV
The standard of T-MOV is UL1449, the specific terms of the tripping performance of T-MOV are as follows:
Permanently connected to the SPD, the maximum current for the voltage test is 10A, so there is still a blind spot in the circuit. When the current in the circuit is 10A-30A, T-MOV burns.
Video 2: added 1000V to the loop, the voltage-sensitive fired when it was 20A.
An effective solution
To solve this problem completely, we need an ideal electronic component with the following properties:
1. The lightning strike can be passed normally, and the operating frequency (1-50a) shows the open circuit failure;
2. The time of the cut-off circuit is defined by different frequency current. Under this current time, pressure sensitivity can be tolerated
3. Since the impedance is uncertain after the pressure-sensitive breakdown, the heat is not controlled, so it can\'t rely on the pressure sensitive heat to cut the circuit.
Fail-safe GDT can meet the three points into action (performance, and can be quickly cut off the circuit, the power frequency approached gas discharge tube below the graph is open circuit failure of power frequency electric current and disconnection time test curve
Video 3: added 1000V to the loop, the Fail-safe
GDT cut off the circuit in 0.68s when it was 20A.
Video 4: added 1000V to the loop, the Fail-safe
GDT cut off the circuit in 0.52s when it was 40A.
It is determined by the internal structure of the Fail-safe GDT
which can quickly break the start frequency current without relying on external
heat.
Conclusion
General AC power supply three plus one solution and T - MOV scheme
still have a blind point to cause a fire. However, the Fail-safe GDT can solve
this problem, it is recommended to use between common mode and differential
mode with the voltage dependent resistor in series.